Flame Detection
A flame detector responds either to radiant energy visible to the
human eye (approx. 4000 to 7700 A) or
outside the range of human vision. Similar to the human eye, flame
detectors have a 'cone of vision', or viewing angle, that defines
the effective detection capability of the detector. FIGURE
With this constraint , the sensitivity increases as the angle of
incidence decreases. Such a detector is sensitive to glowing embers,
coals, or flames which radiate energy of sufficient intensity and
spectral quality to actuate the alarm. Each type of fuel, when burning,
produces a flame with specific radiation characteristics. A flame
detection system must be chosen for the type of fire that is probable.
For example an ultraviolet (UV) detector will respond to a hydrogen
fire, but an infrared (IR) detector operating in the 4.4 micron
sensitivity range will not. FIGURE It is imperative, therefore,
that a qualified fire protection engineer be involved in the design
of these systems, along with assistance from the manufacturer's
design staff.
Due to their fast detection capabilities, flame detectors are generally
used only in high-hazard areas, such as fuel-loading platforms,
industrial process areas, hyperbaric chambers, high-ceiling areas,
and atmospheres in which explosions or very rapid fires may occur.
Because flame detectors must be able to 'see' the fire, they must
not be blocked by objects placed in front of them. The infrared-type
detector, however,has some capability for detecting radiation reflected
from walls.
UV Flame Detectors
IR Flame Detectors
___________________________________________________________________
UV Flame Detectors
Ultraviolet (UV) detectors generally use either a solid-state device,
such as silicone carbide or aluminum nitride, or a gas-filled tube
as the sensing element. UV detectors are essentially sensitive to
both, sunlight and artificial light. A UV flame radiates in the
1850 to 2450 angstrom range. Virtually all fire emit radiation in
this band, while the sun's radiation at this band is absorbed by
the Earth's atmosphere. The result is that the UV detector is solar
blind, meaning it will not cause an alarm in response to radiation
fromthe sun. The implication of this feature is that it can easily
be used both indoors and outdoors.
UV detectors are sensitive to most fires, including hydrocarbon,
metals, sulfur, hydrogen, hydrazine, and ammonia. Arc welding, electrical
arcs, lightning, X-rays used in nondestructive metal testing equipment,
and radiaacctive materials can produce levels that will activate
a UV detection system. The presence of UV-absorbing gases and vapors
will attenuate the UV radiation from a fire, adversely affecting
the ability of the detector to 'see' a flame. Likewise, the presence
of an oil mist in the air or an oil film on the detector window
will have the same effect.
UV/IR Flame Detector
An ultraviolet/infrared flame detectorconsists of an UV and single-frequency
sensor, paired together to form one unit. The two sensors individually
operate the same as described in the UV and IR sections, but additional
circuitry processes signals from both sensors. A fire alarm is produced
only when both sensors detect a fire. The result is that a UV/IR
system has better false alarm rejection capabilities than either
detector by itself. Since the UV/IR detector pairs two sensor types,
it is subject to the limitation of both.
___________________________________________________________________
IR Flame Detectors
An infrared (IR) detector basically is composed of a filter and
system used to screen out unwanted wavelengths and focus the incoming
energy on a photovoltanic or photoresistive cell sensitive to infrared
radiation. IR flame detectors can respond to the total IR component
of the flame alone or in combination with flame flicker inthe frequency
range of 5 to 30 Hz.
A major problem in the use of infrared detectors receiving only
IR radiation is the possible interference of solar radiatino in
the infrared bandwidth. When detectors are located in places shielded
from the sun, such as vaults,then filtering and/or shielding
the unit from the sun rays is unnnecessary.
IR detectors are sensitive to most hydrocarbon fires (liquid, gases
and solids). Fires, such as burning metals, ammonia, hydrogen, and
sulfur do not emit significant amounts of IP radiation in the 4.4
micron sensitivity range of most IR detectors. Thorough planning
is required to aplly IR fire detctors to non-hydrocarbon fueled
fire applications.
A buildup of ice and water film on the detector viewing window
will greatly reduce its sensitivity. IR detectors are less affected
by smoke, oil, and certain gases and vapors than UV Detectors.
|